1. Determine
the volume of your engine compartment in cubic feet or cubic meters, L x
W x H. Do NOT deduct for engines, fixed tanks, or other equipment.
2. Select the clean agent that you
require: FE-241 or HFC-227ea.
FE-241 (Chlorotetrafluoroethane) is
approved for unoccupied spaces such as engine rooms and is approved
for use in the United States.
HFC-227ea (Heptafluoropropane) is
approved for occupied spaces and is also approved for use in Europe.
3. Based on steps 1 and 2, choose your
model from the Model/Size Chart.
Example: CG2-950-227 = automatic
discharge,
950 cubic feet coverage, HFC-227ea extinguishing agent.
NOTE: When in doubt, always select the
larger model size for adequate protection.
WARNING: Diesel-powered craft require
installation of an Engine Shutdown System.